TROUBLESHOOTING
GUIDE
FOR HEAT PUMP BOOSTERS
MODELS: HPB11, HPB15, & HPB22
Zobrazit stránku 0
1 2 3 4 5 6 ... 11 12

Shrnutí obsahu

Strany 1 - TROUBLESHOOTING

V3 TROUBLESHOOTING GUIDE FOR HEAT PUMP BOOSTERS MODELS: HPB11, HPB15, & HPB22

Strany 2 - TABLE OF CONTENTS

Page 8 EXPLODED VIEW DIAGRAM

Strany 3 - Function: Core Charging

Page 9 HPB PARTS LIST NOTE: When ordering replacement parts, please include unit model number and serial number. DWG. REF. NO. DESCRIPTION HPB

Strany 4 - Problem: Unit undercharges

Page 10 DWG. REF. NO. DESCRIPTION HPB11 ITEM NO. HPB15 ITEM NO. HPB22 ITEM NO. 39. Core Blower Wheel 1020002R 1020002R 1020002R 40. Slam Gate In

Strany 5

PREFACE This guide contains instructions for troubleshooting the Steffes Corporation room heating units: Models HPB 11, HPB 15, and HPB 22. In compi

Strany 6 - Function: Air Delivery

Page 1 Heat Pump BoosterFunction: Core ChargingProblem: Unit will not charge (Unit has no core charge) or Control Board lights are off.Before startin

Strany 7 - Problem: Blower does not run

Page 2 Heat Pump BoosterFunction: Core ChargingProblem: Unit underchargesBefore starting any of the procedures below, check voltage on load side of a

Strany 8 - HPB11B, HPB15B and HPB22B

Page 3 Heat Pump BoosterFunction: Core ChargingProblem: Unit overcharges on warm daysBefore starting any of the procedure below, check voltage on load

Strany 9

Page 4 Heat Pump BoosterFunction: Air DeliveryProblem: Cool discharge airBefore starting any of the procedure below, check voltage on load side of

Strany 10 - EXPLODED VIEW DIAGRAM

Page 5 Heat Pump BoosterFunction: Air DeliveryProblem: Blower does not runBefore starting any of the procedure below, check voltage on load side of a

Strany 11 - HPB PARTS LIST

DISCHARGE AIR Check-Out Procedure Models: HPB11B, HPB15B and HPB22B Page 6 CHECK OUT PROCEDURE: The failure of the melt link is often the result of

Strany 12

Discharge Air Check Out Procedure Continued… Page 7 15. Energize the control circuit and check the #4 yellow LED light on the interface board. It